Installation & User Manual

E-2100012.0
Indie 12/User Manual

Indie 12: 12kW Split-Phase Off-Grid Solar Inverter

Owner's & Operator's Manual V1.0

SKU: E-210001Rev 1.0Panel firmware 0.0.26

Terms Used in This Manual

PV
Photovoltaic, meaning the solar array connected to the inverter
MPPT
Maximum Power Point Tracking, the circuit that extracts the most available power from a solar array
BMS
Battery Management System, the circuit board inside a smart battery that monitors and protects the cells
SOC
State of Charge, how full the battery is, expressed as a percentage
SBU
Solar, Battery, Utility, the output priority that uses the grid only as a last resort
Bypass
Passing utility power straight through to the loads instead of inverting
HV bus
The internal high-voltage DC link shared by the inverter, MPPT and battery stages
Absorption
The constant-voltage charge stage held after bulk charging completes
Float
The lower maintenance voltage held once the battery is full
Dry contact
A voltage-free relay contact, carrying no voltage of its own, used to switch an external circuit
AHJ
Authority Having Jurisdiction, the local body that inspects and permits the installation

About This Manual

This manual is your reference for the Indie 12, a 12kW split-phase off-grid solar storage inverter. It covers installation, wiring, the touchscreen control panel, every setting the panel exposes, and what to do when the unit reports a fault. It is written for installers, technicians, and owners who want to understand the system they are running.

Read this manual before you install, wire, or power on the inverter. This equipment switches high voltage on both its DC and AC sides. It is safe when installed correctly and dangerous when it is not. Most field failures trace back to a skipped installation step rather than a manufacturing defect.

Built and Programmed in the United States

The Indie 12 is designed, programmed, and manufactured in the United States with no foreign entity control over the hardware, software, or supply chain. The control panel firmware, the inverter firmware, and the update service that delivers both are ours. That matters for projects with federal incentive or procurement requirements, and it means the settings documented here reflect the software actually shipping on your unit rather than a rebadged reference design.

How the Settings Pages Behave

Values are read live from the inverter each time a settings page opens. Changing a control writes it back over RS485 and then re-reads it to confirm the inverter accepted the change. If a value snaps back to its previous setting, the inverter refused the write, and the reason is usually documented alongside that row in this manual.

Liability Notice

Failure to follow the procedures in this manual may result in injury, death, or property damage. By installing and using this product, you acknowledge and accept all terms in this document. This manual is updated periodically; always verify you have the latest revision.

Specifications

Inverter Output

Rated Output Power (split-phase)12,000 W / 12,000 VA
Rated Output Power (single-phase)6,000 W / 6,000 VA
Rated Output Voltage120 VAC (L1-N, L2-N) / 240 VAC (L1-L2)
Selectable Output Voltage100 V, 105 V, 110 V, 120 V
Output Frequency50 Hz or 60 Hz, 60 Hz default
Output WaveformPure sine wave
Output Voltage AccuracyPlus or minus 5%
Output Frequency AccuracyPlus or minus 0.3 Hz
Power Factor1
Maximum EfficiencyGreater than 91%
Motor Load Capability6 HP
Transfer Time (bypass to inverter)10 ms typical
Phase ConfigurationsSingle-phase, split-phase, parallel, and three-phase array

AC Input

Rated Input Voltage120 VAC (L1-N, L2-N) / 240 VAC (L1-L2)
Input Voltage Range90 VAC to 140 VAC per phase
Input Frequency Range47 to 55 Hz on 50 Hz, 57 to 65 Hz on 60 Hz
Max AC Input Current (settable)0 to 63.0 A, default 63.0 A
AC Input Range ModesAppliance (wide) or UPS (narrow)
Bypass Circuit Breaker2-pole, 63 A per leg
Overload and Short Circuit ProtectionCircuit breaker

Solar (PV) Input

MPPT Trackers2, tracking independently
Max PV Open Circuit Voltage500 VDC
MPPT Operating Voltage Range125 VDC to 425 VDC
Max PV Input Power5,500 W + 5,500 W
Max PV Input Current22 A + 22 A

Never exceed the PV open circuit voltage limit

Size every string so its open circuit voltage stays under the maximum in all conditions, including the coldest morning of the year, when panel voltage is at its highest. Exceeding this limit damages the MPPT stage, and damage caused by an oversized array is not covered by warranty.

String Voltage Calculator

Panel Voc is rated at 25°C, and Voc rises as temperature falls. A string that measures comfortably under the limit on a mild afternoon can exceed it at dawn in January. Enter your panel figures and the coldest temperature the site sees to check the worst case.

V

From the panel datasheet, open circuit voltage

% / °C

Normally negative, for example -0.27

Per string, on one tracker

Record low at the site, not the average winter low

Corrected Voc per panel

54.18 V

String Voc at -10°C

433.4 V

Headroom to 500 V

66.6 V

Within the limit

433.4 V at -10°C, leaving 66.6 V of headroom. This tracker accepts up to 9 panels in series at this temperature.

Operating voltage sits well below Voc once the array is loaded. For the MPPT to track, the string should operate within 125 V to 425 V, so a string sized only to clear the Voc ceiling can still be too small to track well in hot weather. Check the Vmp figures on your datasheet as well.

This is a planning aid, not a substitute for the datasheet

The calculation uses the standard linear temperature correction from 25°C. Use the record low for the site rather than a typical winter morning, and confirm the result against your panel datasheet and local code before ordering. Some jurisdictions require a specific design temperature.

Battery and Charging

Nominal Battery Voltage48 V nominal (51.2 V lithium pack)
Supported Battery TypesUser Defined, CAN BMS, RS485 BMS, Sealed (AGM), Flooded, Gel, LFP 14S / 15S / 16S
Max Total Charge CurrentUp to 180 A, 200 A or 240 A depending on unit rating; default 60.0 A
Max Utility Charge CurrentUp to 100 A, 120 A or 140 A depending on unit rating; 140 A on the 12kW; default 30.0 A
Battery Capacity Setting0 to 400 Ah, default 100 Ah
Absorption Voltage48.0 to 58.4 V, default 57.6 V
Float Voltage48.0 to 58.4 V, default 55.2 V
Over-discharge Cutoff40.0 to 48.0 V, default 44.0 V
Charge Source OptionsUtility First, Solar First, Solar + Utility, Solar Only

Communication

Panel LinkRS485 Modbus between the touchscreen panel and the inverter
RS485 Address1 to 254, default 1, read-only from the panel
Battery BMSRS485 or CAN, selected by Battery Type
Service PortUSB-B, shares the inverter link with the panel
WirelessWi-Fi on the panel, used for firmware updates and network time
Dry Contact5 V battery status signal output, plus one voltage-free changeover contact (NO / NC / COM). Generator control not yet implemented in firmware
Units in ParallelUp to 6

Physical and Environmental

Dimensions (L x W x D)610 mm x 443 mm x 144 mm (24.0 x 17.4 x 5.7 in)Not confirmed
Weight28 kg (62 lb)
Enclosure RatingIP20, indoor use only
Operating Temperature-10°C to 55°C (14°F to 131°F)
Storage Temperature-25°C to 60°C (-13°F to 140°F)
Humidity5% to 95%, non-condensing
CoolingForced air, variable speed fan
Noise60 dB or less

Enclosure dimensions are pending confirmation and are struck through until measured on a production unit.

Safety Instructions

Signal Words

Four signal words appear throughout this manual and on the product labels. They are not interchangeable.

DANGER

A hazardous situation that will result in death or serious injury if ignored.

WARNING

A hazardous situation that may result in death or serious injury if ignored.

CAUTION

A hazardous situation that may result in mild or moderate injury if ignored.

NOTICE

An operating tip, or a practice that can damage equipment without injuring anyone.

DANGER: High voltage on both sides

This inverter connects to a solar array, a battery bank, and utility power. Each of these is an independent energy source, and switching off one does not de-energize the others. A solar array produces voltage whenever light falls on it and cannot be switched off at the panel.

Before opening the terminal cover, isolate all three sources at their disconnects, then verify with a meter that the terminals are dead. Never open the terminal cover or connect and disconnect wiring while the inverter is running.

Who Should Install This Equipment

Installation involves service-entrance-rated conductors, high-voltage DC strings, and a bonding decision that interacts with your service panel. This work should be carried out by a qualified professional who is licensed for electrical work in your jurisdiction and familiar with battery-based energy storage.

Owners who want to understand and adjust their own system will find every setting documented in this manual, and the touchscreen is designed to be used without training. Operating the panel is a different task from wiring the unit, and this manual separates the two deliberately.

Required PPE and Tools

Personal Protection

  • Insulated gloves rated for the system voltage
  • Safety glasses or a face shield
  • Non-conductive footwear
  • No rings, watches, or metal jewelry

Tools

  • Insulated hand tools
  • Calibrated torque wrench or torque screwdriver
  • True RMS multimeter rated for the DC bus voltage
  • Wire strippers and crimpers sized for the conductors
  • Electric drill for the mounting holes

Do's and Don'ts

Do

  • Comply with local codes and the requirements of your AHJ
  • Size conductors and protective devices to code for the currents in this manual
  • Switch off every source before and during installation work
  • Verify polarity on the battery and PV connections before energizing
  • Leave the clearances in the planning section clear at all times
  • Keep the top vents clear, and blow the unit out periodically in dusty environments

Do Not

  • Install near flammable materials or in a potentially explosive area
  • Install the inverter in an enclosed space shared with vented lead-acid batteries
  • Install outdoors, in direct sunlight, or anywhere damp
  • Open the terminal cover while the unit is operating
  • Connect or disconnect any wiring while the unit is operating
  • Exceed the PV open circuit voltage limit
  • Open the unit while any source is connected, or attempt internal repair without the training to do it

Shipping & Receiving

What's in the Box

ItemQty
Indie 12 inverter, with the touchscreen display integrated1
Quick start guide1

That is the whole box. The display is built into the unit and is not a separate item to fit.

Recommended Accessories, Sold Separately

Order these alongside the inverter if your installation needs them.

AccessoryWhen you need it
Parallel communication cableRequired for any multi-unit system. One cable per link in the chain, so a group of three units needs two.
Mounting hardwareFasteners and wall anchors suited to what you are mounting into. Choose these for your wall rather than assuming a generic set will hold.

Mounting hardware is deliberately not included

The right fastener depends entirely on what you are fixing to, whether that is timber studs, masonry, concrete, or steel. A generic set shipped in the box would be wrong for most installations and would invite someone to use it anyway on a wall it cannot hold. Specify hardware rated for the weight of the unit in your wall type.

Inspection After Receipt

Inspect the unit before the carrier leaves, and before you sign anything. Shipping damage claims are far easier to resolve when the damage is noted on the delivery paperwork.

  1. Photograph the packaging as delivered, including any crushed corners or puncture marks.
  2. Check the carton and the unit for dents, cracks, and impact damage.
  3. Confirm the model and serial number on the label match your order.
  4. Check the touchscreen glass for cracks or delamination.
  5. Confirm the quick start guide is present, and that any accessories you ordered separately have arrived.
  6. Note any damage on the delivery receipt before signing, then contact your distributor.

Do not install a unit with visible impact damage, even if it appears to power on. Internal damage to the DC bus capacitors or the heatsink mounting is not always visible from outside, and installing a damaged unit can void the warranty.

Installation Planning

The Indie 12 is rated IP20 and is for indoor use only. Choose the location before you drill anything, because the wrong spot causes problems that are expensive to correct later: nuisance over-temperature shutdowns, a screen nobody can read, or conductors that are longer than they need to be.

Structural Support

A solid wall that can carry the full weight of the unit indefinitely. Mount into structure rather than drywall alone. Do not mount on a wall shared with a bedroom if fan noise matters to you.

Mounting Height

Set the touchscreen roughly at eye level. The panel is the primary interface for the system and it is used standing up. A unit mounted near the floor is legible only from a crouch.

Ventilation and Clearance

The unit is force-cooled by variable speed fans and pushes real heat under load. Leave clear space on all sides and above, and never stack storage against it. Restricted airflow is the most common cause of over-temperature derating.

Ambient Temperature

Keep the space within the operating range in the specifications. The inverter reduces output power to protect itself as it approaches its limits, so a hot closet costs you capacity on exactly the days you need it.

Moisture and Air Quality

Avoid damp locations and direct sunlight. The top vents are unfiltered, so in dusty or agricultural environments dust reaches the inside of the unit. Plan for access to blow it out, and expect to do so more often.

Battery Proximity

Keep DC runs short, because battery conductors carry the highest currents in the system. Do not share an enclosed space with vented lead-acid batteries, which release hydrogen while charging.

DANGER: Do not install in these locations

Near highly flammable materials, in a potentially explosive atmosphere, or in an enclosed space shared with vented lead-acid batteries.

Plan the Wi-Fi coverage too

The panel uses Wi-Fi for firmware updates and network time. A mechanical room at the far end of the property is a common dead spot. Check signal at the mounting location before committing, and note that the panel offers a restart after saving a network in order to finish connecting.

Mounting & Mechanical

Before publishing: add figures and photographs

The sequence below is confirmed. Still needed: exact hole spacing, minimum clearance dimensions, terminal torque values, and photographs of the lower mounting holes, which are the hardest part of the sequence to judge without a picture.

Wall Mounting

  1. 1

    Mark the four mounting holes. Use the mounting template or the unit itself to transfer the pattern to the wall. Check level before drilling, because the unit is heavy enough that correcting a crooked mount means re-drilling.

  2. 2

    Drill and set the upper anchors. Install the two upper expansion anchors and leave them proud enough for the unit to hang on them.

  3. 3

    Lift the unit onto the upper anchors. This is a two-person lift. Keep the unit upright and do not use the touchscreen bezel or the terminal cover as a handhold.

  4. 4

    Secure the lower fasteners. Fit and tighten the two lower screws, then confirm the unit sits flat against the wall with no rocking.

  5. 5

    Verify clearances. Re-check that the ventilation clearances are still satisfied now that the unit is in place, including anything the installation added such as conduit runs.

Terminal Cover and Ventilation

The terminal cover comes off with a screwdriver. It stays off during wiring and goes back on before the unit is energized.

Ventilation is through open vent holes along the top of the enclosure. There is no filter or screen to remove, and nothing on the outside of the unit is a serviceable part. Keep the vents clear and unobstructed, and do not set anything on top of the unit.

Open vents mean dust gets in

Because the vents are unfiltered, airborne dust reaches the inside of the unit rather than collecting on a screen you can wash. In dusty, agricultural or workshop environments that builds up over time, insulates the heatsinks, and eventually shows as over-temperature faults on the MPPT or inverter stage, alarm codes 19 and 20. The remedy is periodic blowing out with canned air, covered in the .

Electrical Installation

DANGER: Isolate every source first

Open the battery disconnect, the PV disconnect, and the AC input breaker before removing the terminal cover. Verify each set of terminals is dead with a meter. A solar array remains live in daylight regardless of what the inverter is doing, and battery banks have no off switch of their own beyond the disconnect you install.

Conductor and breaker sizing is a code decision

The table below gives the currents each connection must carry and a starting point for conductors and protective devices. Final sizing depends on your conductor type, ambient temperature, bundling, run length, and local code. Size to code for the currents shown, and have a qualified professional confirm the result.

Conductor and Breaker Reference

ConnectionMax CurrentConductorBreaker
PV input, per tracker22 A10 AWG (5 mm²)2-pole 25 A
Battery240 A2/0 AWG (67 mm²)2-pole 250 A
AC input, split-phase63 A (L1/L2/N)6 AWG (13 mm²)3-pole 63 A
AC input, single-phase63 A (L1/L2), 126 A (N)6 AWG L, 2 x 6 AWG N2-pole 125 A
AC output, split-phase63 A (L1/L2/N)6 AWG (13 mm²)3-pole 63 A

About the AC Terminals

The AC input and output terminals are DIN rail terminal blocks. Ordinary stranded building wire lands bare, with no ferrule needed, and none are supplied with the unit. Strip 6 mm to 8 mm and clamp the conductor directly.

Fine-stranded cable is the exception

Standard building wire has relatively few, relatively thick strands and clamps reliably as bare copper. Very fine stranded conductors are different: welding cable, DLO, and similar highly flexible cable pack hundreds of hair-thin strands into the same cross-section.

Those strands spread and escape under a clamping screw. Some end up outside the clamp entirely, which reduces the copper actually carrying current and can leave stray strands loose in the enclosure. If you are landing that kind of cable, crimp a ferrule onto it first so the strands stay together as one solid pin.

Single-phase neutral takes two conductors, not one larger one

In single-phase mode the neutral carries up to 126 A, double the line current, because both legs return through it. The AC terminal will not accept anything larger than 6 AWG, so the neutral is landed as two 6 AWG conductors in parallel rather than a single heavier cable. Both must be the same length and gauge so they share current evenly. Do not attempt to force a larger conductor into the terminal.

Wiring Order

Ground first, then the high-current DC, then AC, then signal wiring. Working in this order means the chassis is bonded before anything else is landed.

  1. 1

    Grounding. Bond the chassis grounding screw to the grounding bus bar with a conductor sized to code. This connection is made first and removed last.

  2. 2

    Battery. Land the positive and negative battery conductors on their marked terminals through an external disconnect. Verify polarity with a meter before the disconnect is closed. Reversed polarity damages the unit and is not a warranty repair.

  3. 3

    PV input. Land each array on its own tracker, PV1 and PV2, observing polarity. Confirm each string open circuit voltage with a meter before connecting, and check it against the maximum in the specifications using the coldest temperature the site sees.

  4. 4

    AC input. Land line, neutral, and ground from the utility or generator in the marked sequence. In split-phase the input must be split-phase, matching the output configuration.

  5. 5

    AC output. Land the load conductors in the marked sequence. Strip 6 mm to 8 mm, no more, so no bare conductor is left outside the terminal.

  6. 6

    Signal wiring. Land the battery BMS cable on the RS485 or CAN port, the parallel cable if used, and the dry contact wiring. Signal conductors take 0.2 mm² to 1.5 mm².

  7. 7

    Torque and close up. Torque every terminal to specification with a calibrated tool, re-check polarity on the battery and PV connections, then refit the terminal cover before energizing.

Neutral and Bonding

This version has no neutral-to-ground bonding relay

The inverter contains a neutral connection relay, which switches the neutral path. It does not bond neutral to ground. The Grid page carries a row labeled Neutral-Ground Bond, and that label overstates what the hardware does on this version.

Do not rely on the inverter to establish the neutral-to-ground bond. The bond has to come from your wiring, using one of the two arrangements below.

Which arrangement applies depends on whether the source feeding the inverter is already bonded upstream.

Non-bonded source

Where no bond exists upstream, establish the neutral-to-ground bond in the load panel fed by the inverter. That panel becomes the single bonding point for the system.

Upstream bonded source

Where the supply is already bonded upstream, do not add a second bond. Land the input neutral and the output neutral on the same bus bar so both sides share one neutral reference and the existing upstream bond serves the whole system.

One bond, and only one

The failure modes sit either side of this. No bond anywhere leaves the system without a ground reference. Two bonds create a parallel neutral path, putting return current on the grounding conductor. Decide which arrangement applies before energizing, follow your local electrical code, and have a qualified professional confirm it.

Dry Contact Port

The port carries two separate things: a low-voltage status signal output that follows the battery, and a voltage-free changeover contact intended for generator control. Only the status output is driven by firmware today.

Status Signal Output

A 5 V logic-level signal between pin 3 and pin 1. It reads 5 V while the battery is charging or discharging normally, and falls to 0 V when the battery reaches the Discharge Limit Voltage set on the Battery page. Use it to tell external equipment that the pack has hit its floor.

Battery statePin 3 to pin 1
Charging or discharging normally5 V
At the Discharge Limit Voltage0 V

Before publishing: state the output current limit

Insert the maximum current this output can source. Until that figure is confirmed, the guidance below is written conservatively.

Interim guidance: treat this as a logic-level signal only. Drive a high-impedance input, an optocoupler, or the base of a small transistor. Do not use it to power a relay coil, an indicator lamp, or anything else that draws meaningful current. If the load needs more than a few milliamps, buffer it.

Changeover Contact

A voltage-free relay contact with three terminals. It carries no voltage of its own and switches whatever circuit you wire through it.

TerminalDescription
COMCommon pole of the changeover contact. The circuit you are switching passes through here.
NONormally open. Open while the relay is at rest, closed to COM when it operates.
NCNormally closed. Closed to COM while the relay is at rest, open when it operates.

Generator control is not implemented yet

This contact is intended for automatic generator start and stop, and the hardware is fitted for it. The firmware does not drive it yet, so it does not change state in response to battery voltage, state of charge, or any other condition.

Do not design a system that depends on automatic generator starting today. If you need generator support now, plan for a manual or external controller, and treat this contact as provision for a future firmware release.

Wiring the Port

Push the terminal release back with a small screwdriver and insert the conductor. Signal conductors of 0.2 mm² to 1.5 mm² suit this connector. Wire it during installation if you expect to use either function later, since running the cable now is far easier than pulling it after the unit is commissioned and the terminal cover is on.

Respect the contact rating

Both functions on this port are signal-level. Use the changeover contact to switch a generator control input or a pilot relay, never to carry load current directly. Confirm the contact rating before connecting anything, and fit an interposing relay if the circuit you are switching draws more than the contact allows.

Parallel Systems

Up to six units can run together, either paralleled on the same phase for more power or arranged across phases to build a split-phase or three-phase system. Each unit is told its role through the Phase Configuration setting on its own System page.

Rules That Apply to Every Parallel Build

Solar arrays stay independent

Every inverter needs its own array, and within a single inverter PV1 and PV2 must be independent of each other. Never parallel arrays across trackers or across units.

The battery bank is shared

All units connect to the same battery bank, positive to positive and negative to negative. Keep the conductor runs equal in length and gauge so the units see the same voltage. Unequal runs show up as alarm code 38, parallel battery mismatch.

One AC source, common to all

Every unit must see the same utility or generator input. Multiple separate AC sources into a parallel group damages connected equipment and raises alarm code 39.

Neutral and ground are common

Neutral connects to neutral and ground to ground across the whole group. Line conductors are tied together only among units assigned to the same phase, never across different phases.

Communication is a daisy chain

The shielded parallel cable runs out from one unit into the next, male connector to female connector, along the chain. Tighten the connector screws so a cable cannot work loose in service, since an intermittent link produces synchronization faults that are hard to trace.

Firmware versions must match

Units running different firmware raise alarm code 42. When you update one unit in a group, update them all.

Assigning Phase Configuration

Each unit is set individually on its own touchscreen, under System, then Phase Configuration. The nine options cover standalone operation, paralleling for power, and multi-unit phase assignment.

Use caseSetting on each unit
One unit, 120 V onlySingle-phase (both legs, 120V)
One unit, 120/240 V split-phaseSplit-phase 120/240V
Two units for more power on one phaseParallel: Both inverters same phase
Two units covering both legsParallel: Both inverters both phases
Split-phase array built from separate unitsSplit-phase array: this inverter L1 only, and L2 only on the other
Three-phase systemThree-phase: this inverter A phase only, then B, then C

Phase Configuration can only be changed in standby, and the inverter restarts

The inverter refuses the write while it is running, and when the value does change the unit restarts. Both facts affect loads, so make this change during commissioning or a planned outage rather than with the house running on it. Setting it inconsistently across a group produces alarm code 45.

DANGER: Power the whole group down before adding a unit

To add an inverter to a system that is already running, disconnect battery, PV, AC input, and AC output on every unit in the group, and confirm all of them are fully powered off before making any connection. Adding a live unit to a live group risks damage to the equipment and injury to the person doing it.

Power Up & Shutdown

The order matters. Bringing the battery up first lets the DC bus pre-charge in a controlled way before any solar or utility source is introduced, and starting loads smallest first avoids a cold start into a large inrush.

Power-Up Procedure

  1. 1

    Inspect the installation. Confirm the terminal cover is refitted, the top vents are clear, every terminal is torqued, and battery and PV polarity have been verified with a meter.

  2. 2

    Close the battery disconnect. This is the first source to bring up.

  3. 3

    Switch the inverter on. The touchscreen and indicators light up. The panel shows Waiting for initialization while it establishes its link to the inverter, then the home screen appears with Live Data, Settings and Graphs.

  4. 4

    Watch the DC bus come up. Open Live Data. During soft start the unit sits in standby and reports DC bus soft start, N% complete. This is normal and clears on its own.

  5. 5

    Close the PV disconnect. Solar input comes up next. The MPPT box on Live Data should begin reporting voltage and power.

  6. 6

    Close the AC input breaker. The Grid box should report voltage and the input relay should show as closed if the source is within the accepted window.

  7. 7

    Close the AC output breaker. The output relay closes and the loads are live.

  8. 8

    Start loads one at a time, smallest first. Bringing up the largest motor load into a cold system is the most likely way to trip an overload on first start.

  9. 9

    Check for alarms. Confirm the Alarms screen reads No active alarms. If anything is showing, resolve it before leaving the system unattended. See the .

Shutdown Procedure

  1. Shut down the connected loads.
  2. Open the AC output breaker.
  3. Open the AC input breaker.
  4. Open the PV disconnect.
  5. Switch the inverter off.
  6. Open the battery disconnect.

Stored energy remains after shutdown. The DC bus capacitors hold a charge after every source is isolated. Allow the unit to sit before opening the terminal cover, and verify with a meter rather than assuming.

Touchscreen Panel

The panel is the whole interface. There are no buttons to press and no numbered parameter codes to look up. The home screen offers three apps: Live Data, Settings, and Graphs.

The Settings Dashboard

Settings opens a dashboard of eight tiles. Five of them read and write the inverter itself, and three are panel-local, meaning they are stored on the display and survive independently of the inverter.

#TileNotes
1OutputWrites to the inverter
2ChargingWrites to the inverter
3BatteryWrites to the inverter. Contains two sub-pages
4GridWrites to the inverter
5ScheduleWrites to the inverter
6SystemPanel-local, apart from Phase Configuration
7Display / SoundPanel-local, apart from the Beeper row
8CommunicationPanel-local, with one read-only inverter row

Pages Reached by Tapping a Row

Some pages are not tiles. They appear as a row on another page and open when tapped, and they only appear at all when they are relevant.

  • BMS Settings, from a row on the Battery page. Appears only when the battery type selects a BMS.
  • Fallback Settings, from a row on the BMS Settings page.
  • About and Firmware Update, from the System page.
  • Wi-Fi, from the Communication page.

The Status Line

Every page that talks to the inverter carries a status line at the top. While a page is loading it reads Reading settings from inverter.... Values are read live each time the page opens, so what you see is the inverter current state rather than a cached copy.

Why a setting sometimes snaps back

Changing a control writes it over RS485 and then re-reads it to confirm. If the inverter refuses the write, the displayed value returns to what the inverter actually holds. The common causes are documented alongside the rows they affect: Phase Configuration is refused unless the unit is in standby, and the charge voltages can be refused while a BMS is connected and in control.

Grayed-out tiles mean the USB port has the link

The panel and the USB service port share a single connection to the inverter and only one can hold it at a time. While USB tool access is switched on, a banner reads USB tool mode: panel link released and every tile that needs the inverter is grayed out. Switch it back off to return the link to the panel.

Live Data Screen

Live Data is a power-flow diagram of the whole system. Each box is a real stage inside the unit or a real connection outside it, and tapping one opens a detail popup with its measurements. The prompt on screen reads Tap a box for details.

What Each Box Represents

GridThe utility or generator connection at the AC input.
LoadEverything drawing power from the AC output.
BatteryThe battery bank, including state of charge and temperature where a BMS reports them.
InverterThe DC to AC stage between the HV bus and the 120/240 V AC output.
MPPTThe solar input stage, tracking the array for maximum power.
BoostThe bidirectional DC to DC stage between the HV bus and the battery. This is what combines grid and solar charging.
HV busThe high-voltage DC link shared by the inverter, the MPPT solar input, and the battery boost stage.

Operating Mode

The screen reports one of four operating modes: On Grid, On Battery, Standby, or Starting up. The battery separately reads Charging, Discharging, or Idle.

Why the Relays Are Where They Are

The input and output relay states come with a plain explanation, which is usually the quickest way to understand what the system is doing.

Input relay closedGrid is connected and feeding the loads.
Input relay open, grid presentGrid detected but not in use; running from the inverter.
No inputNo grid voltage detected at the input.
Output relay closedOutput is live to the loads.
Output relay openOutput is off; the inverter is not delivering power.

Standby Explanations

When the unit sits in standby, the panel names what is holding it there, in the form Standby, held by: reason. The reasons all concern the internal DC bus.

DC bus soft start, N% completeNormal startup. The bus is pre-charging and the percentage counts up.
DC bus undervoltageThe bus has not reached its working voltage.
DC bus overvoltageThe bus is above its working range.
DC bus imbalanceThe positive and negative halves of the bus differ too much.
DC bus short circuitA short was detected on the internal bus. This one needs service.

Read the second line carefully

Below the reason the panel says either Clears by itself in N s or Will not clear on its own. The condition is still present. The second message is deliberate. It appears when the inverter is showing a countdown that is not actually running, which means waiting will not help and the installation needs looking at.

Startup Messages

Waiting for initialization appears while the panel establishes its link. No response, check inverter link means the panel cannot reach the inverter at all: check that the inverter is powered on, that the RS485 link is intact, and that USB tool access is not holding the link.

Output & Charge Modes

Two settings decide almost everything about how the system behaves day to day. Output Priority decides what powers the loads. Charger Source Priority decides what refills the battery. They are independent, and choosing them together is what tunes the system to a site.

Output Priority

Utility First

Priority: grid, then solar, then battery

The grid carries the loads and keeps the battery topped up. Solar contributes alongside it. The battery is held in reserve and only carries the loads when the grid is unavailable. Choose this where the battery exists for backup rather than for daily savings.

Solar First (default)

Priority: solar, then grid, then battery

Solar carries as much of the load as it can, and the grid makes up any shortfall. The battery stays charged and is not cycled for everyday loads. This uses solar to the maximum while preserving battery life, and suits sites with a stable grid.

Solar / Battery (SBU)

Priority: solar, then battery, then grid

Solar carries the loads, the battery covers what solar cannot, and the grid is the last resort. The system falls back to the grid when the battery reaches the Battery to Utility Voltage threshold, and returns to battery once it recovers past Battery to Inverter Voltage. This maximizes self-consumption and is the mode to choose where grid power is expensive or unreliable.

Charger Source Priority

Solar + Utility (default)

Both sources charge together, solar first with the grid making up the difference. This is the fastest way to refill a bank, and the right choice where you need the battery back to full quickly.

Solar Only

The battery charges from solar and never from the grid. The most economical option where the array is generously sized and the climate cooperates. Be aware that a long overcast spell has no fallback in this mode.

Utility First

The grid charges the battery, and solar charging starts only when the grid is unavailable. Useful where the battery must stay full for backup duty regardless of weather.

Solar First

Solar charges the battery, and the grid takes over only when solar cannot. Uses the array fully during the day and covers the shortfall in the evening. A good fit where grid energy is expensive but you cannot risk an empty bank.

Pair these with the Schedule page for time-of-use billing

If your utility charges different rates through the day, Timed Charging and Timed Discharging let you confine each activity to chosen windows: charge when energy is cheap, run from the battery when it is expensive. See the .

Settings: Output

Every row on this page writes to the inverter. These settings shape the AC output itself and decide how the unit reacts to an overload or an over-temperature event.

Output Priority

Dropdown · default Solar First

Chooses what powers your loads and in what order.

Utility First: uses the grid and keeps the battery topped up.

Solar First: uses PV then grid to save the battery.

Solar / Battery (SBU): runs from solar and battery and only falls back to the grid when they run low.

Output Voltage

Dropdown · 100 / 105 / 110 / 120 V on this model

Nominal AC output voltage. Pick the standard your loads expect.

The panel reads the model and offers only the presets this inverter will accept, so the list you see is shorter than the full range the platform supports.

Output Frequency

Dropdown · 50 Hz or 60 Hz · default 60 Hz

AC output frequency. Use 60 Hz in North America, 50 Hz across most of Europe, Africa and Asia. Match your loads and any grid you tie to.

Power Saving

Switch · default off

Shuts the output down when almost no load is detected and wakes on demand, saving idle power. Turn off if small loads flicker or drop out.

Auto-restart on Overload

Switch · default on

After an overload shutdown, try to restart automatically instead of latching off.

Auto-restart on Over-temp

Switch · default on

After an over-temperature shutdown, restart automatically once the unit cools down.

Bypass on Overload

Switch · default on

On an overload, transfer the load to the utility (bypass) instead of shutting down, when the grid is available.

Match Output Voltage and Frequency to your loads

The panel offers only the presets this model accepts, so the list is shorter than the platform supports. A unit rejects a voltage from the wrong class outright. Set frequency to 60 Hz in North America and 50 Hz across most of Europe, Africa and Asia, and make sure it matches any grid you connect to.

Settings: Charging

This page covers where charging energy comes from and how much the grid may contribute. The battery charge profile itself, meaning the voltages, times and stop conditions, lives on the Battery page instead.

Charger Source Priority

Dropdown · default Solar + Utility

Where battery charging energy comes from: Utility First, Solar First, Solar + Utility together, or Solar Only, which never charges from the grid.

Max Utility Charge Current

Slider · 0 A to rating ceiling · step 0.1 A · default 30.0 A

Maximum battery charge current in DC amps drawn from the utility or generator, separate from the solar limit.

The ceiling is provisioned per unit rather than user-set, and reaches 140 A on the 12 kW model.

Two different current limits, and both apply

Max Utility Charge Current on this page caps only what the charger draws from the grid or a generator. Max Charge Current on the Battery page caps the total from all sources combined. When running on a generator, the utility limit is what keeps the charger from overwhelming it, and Max AC Input Current on the Grid page caps loads and charging together.

Settings: Battery

This is the longest page on the panel and the only one where most rows are conditional. Battery Type is the master control. It decides which of the rows below appear at all, so the page you see depends on the battery you told the inverter you have.

All voltages are whole pack volts

Every voltage on this page is the full 48 V pack voltage, which is what the panel displays. One press of the plus or minus button moves the value by 0.4 V at the pack.

Choosing a Battery Type

Selecting a preset seeds the charge voltages and hides them, because the preset already knows the right values. Selecting User Defined exposes every voltage for manual entry. Selecting CAN BMS Control or RS485 BMS Control is what turns the BMS on and reveals the BMS Settings row.

User DefinedYou set every voltage yourself. All the voltage rows below become visible.
CAN BMS ControlA smart battery governs over the CAN bus. Reveals BMS Settings.
RS485 BMS ControlA smart battery governs over RS485. Reveals BMS Settings.
Sealed (AGM), Flooded, GelLead-acid presets. Absorption and float remain visible so they can be trimmed.
LFP 16S, LFP 15S, LFP 14SLithium iron phosphate presets. Pick the one matching your cell count.

Equalization is for lead-acid only. It is available under User Defined, and should be left off for lithium and gel banks. Running a controlled overcharge on a lithium pack is not a maintenance procedure, it is a way to damage cells.

Battery Page Rows

The Shown when note on each row is not a footnote. An owner with a lithium battery never sees the equalization rows at all, and rows move out of reach entirely once a BMS takes control.

Battery Type

Dropdown

Shown when: Always shown

Selects the charge profile.

Sealed (AGM), Flooded and Gel are lead-acid.

The lithium presets apply their own limits. Pick the one matching your cell count: 14S, 15S or 16S on a 48 V pack.

User Defined lets you set every voltage yourself.

Choosing CAN BMS Control or RS485 BMS Control is what turns the BMS on and reveals the BMS Settings row.

BMS Settings

Opens a sub-page

Shown when: BMS selected

How the inverter talks to a smart battery BMS. The bus itself, RS485 or CAN, is chosen by the Battery Type above rather than inside this page.

Capacity

Stepper · 0 to 400 Ah · step 10 Ah · default 100 Ah

Shown when: Always shown

Rated amp-hour size of the battery bank. Used for state-of-charge estimation and charge limits.

Max Charge Current

Slider · 0 A to rating ceiling · step 0.1 A · default 60.0 A

Shown when: Hidden once a BMS takes control

Total battery charge current in DC amps from all sources combined. Set it at or below the charge rate your battery vendor recommends.

Absorption Voltage

Stepper · 48.0 to 58.4 V · step 0.4 V · default 57.6 V

Shown when: User Defined or lead-acid

Boost and absorption target the charger holds after the bulk stage. This is the full pack voltage.

Absorption Time

Stepper · 5 to 900 min · step 5 min · default 120 min

Shown when: User Defined

How long the charger holds absorption voltage before dropping to float, in minutes.

Float Voltage

Stepper · 48.0 to 58.4 V · step 0.4 V · default 55.2 V

Shown when: User Defined or lead-acid

Maintenance voltage held once the battery is full. Lower than absorption to avoid overcharging.

Boost Recovery Voltage

Stepper · 48.0 to 54.0 V · step 0.4 V · default 52.4 V

Shown when: User Defined

If the battery falls below this the charger returns to boost and absorption.

Equalization

Switch · default off

Shown when: User Defined

Enables a periodic controlled overcharge that balances cells and removes sulfation on flooded and sealed lead-acid banks. Leave off for lithium and gel.

Turning this on reveals the four equalization rows below it.

Equalize Voltage

Stepper · 48.0 to 58.4 V · step 0.4 V · default 57.6 V

Shown when: Equalization on

Equalization voltage target. Higher than absorption, and used only while Equalization is on.

Equalize Time

Stepper · 5 to 900 min · step 5 min · default 120 min

Shown when: Equalization on

How long each equalization runs, in minutes.

Equalize Timeout

Stepper · 5 to 900 min · step 5 min · default 240 min

Shown when: Equalization on

Safety limit: end equalization after this many minutes even if the target was not held.

Equalize Interval

Stepper · 0 to 30 days · step 1 day · default 30 days

Shown when: Equalization on

How often to equalize, in days.

Stop-Charge Current

Stepper · 2.0 to 10.0 A · step 0.1 A · default 2.0 A

Shown when: Always shown

Tail-current threshold. When charge current drops below this at absorption, charging is treated as complete.

Stop-Charge SOC

Slider · 80 to 100 % · step 1 % · default 100 %

Shown when: BMS present

With a BMS, stop charging when state of charge reaches this percentage.

Over-discharge Cutoff

Stepper · 40.0 to 48.0 V · step 0.4 V · default 44.0 V

Shown when: User Defined

The inverter disconnects the load when battery voltage falls to this, protecting the pack from deep discharge.

Over-discharge Delay

Stepper · 5 to 55 s · step 5 s · default 5 s

Shown when: Always shown

How long voltage must stay low before the over-discharge cutoff trips, in seconds. Rides through brief dips.

Over-discharge Recovery

Stepper · 48.0 to 58.4 V · step 0.4 V · default 50.4 V

Shown when: User Defined

After an over-discharge cutoff, restore the load once voltage recovers above this.

Discharge Limit Voltage

Stepper · 40.0 to 52.0 V · step 0.4 V · default 43.2 V

Shown when: User Defined

Hard discharge floor. The inverter will not pull the battery below this.

Low DC Warning

Stepper · 40.0 to 52.0 V · step 0.4 V · default 44.0 V

Shown when: User Defined

Low-voltage warning point. Alerts before the over-discharge cutoff, and does not stop the output.

Battery to Utility Voltage

Stepper · 44.0 to 52.0 V · step 0.4 V · default 46.4 V

Shown when: Hidden once a BMS takes control

In Solar / Battery mode, switch loads to the utility when battery voltage drops to this.

Battery to Inverter Voltage

Stepper · 48.0 to 60.0 V · step 0.4 V · default 52.0 V

Shown when: Hidden once a BMS takes control

After switching to utility, return loads to battery and inverter once voltage recovers above this.

Low SOC Alarm

Slider · 10 to 60 % · step 1 % · default 20 %

Shown when: BMS present

Warns, and can beep, when battery state of charge falls below this level. A heads-up, not a shutdown.

Stop-Discharge SOC

Slider · 0 to 50 % · step 1 % · default 20 %

Shown when: BMS present

With a BMS, stop discharging to protect the battery when state of charge falls to this percentage.

SOC to Switch to Utility

Slider · 0 to 50 % · step 1 % · default 20 %

Shown when: BMS in control

With a BMS, switch loads to the utility when state of charge drops to this percentage.

SOC to Switch to Battery

Slider · 55 to 100 % · step 1 % · default 80 %

Shown when: BMS in control

With a BMS, return loads to the battery once state of charge climbs back to this percentage.

BMS Settings

Reached from the Battery page, and only when the battery type selects a BMS. There is deliberately no bus picker on this page: the choice between RS485 and CAN is made by the Battery Type setting, so change it there rather than looking for it here.

StatusWhat it means
OffNo BMS bus is selected.
MonitoringThe BMS is connected and reporting, but your voltage settings still govern.
In ControlThe BMS governs switchover and the charge and discharge limits.
No CommsA BMS is configured but the link is down.

Status

Read-only

Shown when: Always shown

Reports whether the BMS link is off, monitoring, in control, or not communicating.

Stop on Comms Lost

Switch

Shown when: BMS in control

When the BMS is in control and its link drops: off falls back to the voltage settings and keeps running, on stops the inverter.

Stop on BMS Error

Switch · default on

Shown when: BMS in control

While the BMS is in control, obey its charge and discharge stop signals. Turn off to treat BMS errors as advisory only.

Fallback Settings

Opens a sub-page

Shown when: BMS in control, and Stop on Comms Lost off

The voltage-based settings the inverter falls back to if the BMS link is lost. Hidden when Stop on Comms Lost is on, because a unit set to stop has no fallback to configure.

BMS Protocol

Dropdown

Shown when: A BMS bus is selected

Selects which battery protocol the inverter speaks. The list offered depends on whether the Battery Type chose the RS485 or the CAN bus.

Set it to match your battery, and check the battery documentation for the correct entry.

BMS Charge Mode

Dropdown · default Use my current limit

Shown when: A BMS bus is selected

How the inverter applies the BMS charge and discharge limits. Choose whether your own current limit governs, or the limit the BMS reports.

Leave this at the default unless your battery vendor specifies otherwise.

Setting the BMS protocol

The panel lists the protocols available on whichever bus your Battery Type selected. Choose the entry your battery documentation specifies. If you are not sure which one applies, ask your battery supplier rather than working through the list, because a mismatched protocol usually presents as intermittent communication rather than a clean failure.

Fallback Settings

These are the values the inverter runs the battery on when the BMS is not in control, whether the link was lost or the pack has no BMS at all. They are the same underlying settings as on the Battery page, so the two views always agree. They are split out so you can see plainly what the battery does without the BMS.

RowRangeDefault
Max Charge Current0 A to the unit rating ceiling60.0 A
Absorption Voltage48.0 to 58.4 V57.6 V
Float Voltage48.0 to 58.4 V55.2 V
Over-discharge Cutoff40.0 to 48.0 V44.0 V
Over-discharge Recovery48.0 to 58.4 V50.4 V
Battery to Utility Voltage44.0 to 52.0 V46.4 V
Battery to Inverter Voltage48.0 to 60.0 V52.0 V

Set these at commissioning

While the BMS is connected and talking, it owns the charge voltages, and an edit here may be refused until communication drops. That makes commissioning the practical time to set them, rather than discovering during an outage that the fallback values were never configured.

Settings: Grid

How the inverter treats the incoming utility or generator supply, and two protective functions that sit on the AC side.

AC Input Range

Dropdown · default Appliance (wide)

How wide a utility voltage window to accept before rejecting the source.

Appliance (wide): tolerates weak grids and generators.

UPS (narrow): transfers sooner to protect sensitive electronics.

Max AC Input Current

Slider · 0 to 63.0 A · step 0.1 A · default 63.0 A

Caps total current drawn from the AC input, utility or generator. Set it to your breaker size.

The charger scales back as loads rise, so loads plus charging stay under this figure.

Neutral-Ground Bond

Switch · default off

On this hardware version the relay behind this row switches the neutral connection. It does not bond neutral to ground, despite what the row is called.

Bonding is handled by your wiring rather than by the inverter. See the Electrical Installation section for the two accepted arrangements.

Follow your local electrical code and have a qualified professional confirm the wiring.

Leakage Current Detection

Switch · default off

Residual-current, or ground-fault, detection that trips on leakage current for shock protection.

Set Max AC Input Current to the source, not the load

On utility power this should match your breaker size. On a generator it should match the generator rating, which is usually smaller. The charger scales itself back as house loads rise so that loads plus charging together stay under this figure, which is what stops a generator being stalled by the charger.

Choosing an AC Input Range

Appliance (wide) tolerates weak grids and generators, and is the right default for most sites. UPS (narrow) transfers to the inverter sooner to protect sensitive electronics, at the cost of transferring more often on a soft grid. If a generator keeps getting rejected, Appliance is the setting to be on.

Settings: Schedule

Two independent sections, one for charging and one for discharging, each with an enable switch and up to three time windows. Use them to line the system up with time-of-use pricing: charge when energy is cheap, and run the house from the battery when it is expensive.

Timed Charging

Switch · default off

When on, the battery only charges during the time windows below. Leave off to charge whenever sources allow.

Switching it on reveals Charge 1 Start and Charge 1 End. A plus button adds a second and third window, and a minus button removes one.

Timed Discharging

Switch · default off

When on, the battery only discharges to loads during the time windows below.

Switching it on reveals Discharge 1 Start and Discharge 1 End, with the same plus and minus buttons for up to three windows.

Any time row

24-hour HH:MM

Start or end of this window, 24-hour HH:MM. Tap the minus and plus buttons to set the hour and minute.

How the Time Entry Works

Clock format24-hour HH:MM
HoursStep by 1 and wrap at 23
MinutesStep by 15 and wrap at 45, so only :00, :15, :30 and :45 can be set
Windows per sectionUp to 3. Only the first shows initially; a plus button reveals the next and a minus button removes it
When changes are sentAbout two and a half seconds after the last tap, so holding a button does not flood the link

Set the clock before you set a schedule

The panel takes network time over Wi-Fi, which you can confirm on the Wi-Fi page. A schedule is only as accurate as the clock behind it, so connect the panel to a network before relying on timed charging or discharging.

Settings: System

Mostly navigation, plus the one setting that decides how this unit shapes its output. The page stays reachable while the USB port holds the inverter link, but Phase Configuration grays out in that state because it needs the inverter.

About

Opens a sub-page

Firmware versions, security status and credits.

Firmware Update

Opens a sub-page

Check for and install new panel firmware, and deliver new inverter firmware.

Phase Configuration

Dropdown · nine options

How this inverter shapes its output, alone or as one unit in a stack: single-phase, split-phase, paralleled for more power, or one phase of a multi-unit system.

Changeable only in standby, and the inverter restarts when it changes.

Phase Configuration affects loads twice over

The inverter accepts a change only while it is in standby, and it restarts when the value changes. Loads drop during that restart.

Plan this change for commissioning or a scheduled outage. In a multi-unit system every unit must be set consistently, and a mismatch across the group raises alarm code 45. The nine options and which to use are covered in the .

About

A read-only page with three cards. Firmware shows the panel version and the inverter version, read live. Security shows secure boot, flash encryption and download mode status. Credits carries the product wordmark.

Have both firmware versions from this page to hand when contacting support. Most questions about behavior come down to which version is running, and the inverter and panel are updated separately.

Settings: Display & Sound

Everything here is stored on the display itself and survives a restart, with one exception: the Beeper row is an inverter setting and writes through to the unit.

Language

Dropdown · saved on the panel

Language for the on-screen text. Stored on the panel rather than the inverter.

Temperature units

Dropdown · Celsius or Fahrenheit · default Celsius

Show temperatures in Celsius or Fahrenheit. This only changes how the panel prints them, since the inverter always reports Celsius on the wire.

Brightness

Slider · 10 to 100 % · default 100 %

How bright the screen backlight is.

Dim After

Tap to type seconds · 0 to 600 s · default 60 s

Dim the screen after this long with no touches, to save power. Touch anywhere to wake it.

Enter 0, which displays as Never, to skip dimming.

Turn Off After

Tap to type seconds · 0 to 600 s · default 120 s

Turn the screen off after this long with no touches. Touch anywhere to wake it.

Enter 0, which displays as Never, to keep the screen always on.

Beeper

Dropdown · five options · default All sounds · writes to the inverter

Sets how much the built-in beeper sounds. See the table below for exactly what each option covers.

Dim After and Turn Off After are two stages of the same behavior

The screen dims first, then turns off. Either stage can be disabled on its own by entering 0, which displays as Never. Touch anywhere to wake the screen from either state.

What Each Beeper Setting Covers

SettingPower-on tuneSource changeFaults & warningsTouch clicks
SilentNoNoNoNo
All soundsYesYesYesYes
No source change beepsYesNoYesYes
Warnings onlyNoNoYesNo
Critical alarms onlyNoNoSerious onlyNo

Silent means silent. On Silent the unit will not beep for a critical fault. If the inverter is installed where nobody watches the screen, choose Critical alarms only rather than Silent so a shutdown-level fault still makes a sound.

Settings: Communication

Wi-Fi

Opens a sub-page

Connect the panel to a wireless network.

USB tool access

Switch · default off · not saved across restarts

Releases the inverter link so a computer on the USB service port can use it.

The panel and the USB port share one link and only one can hold it at a time, so live data stops until you switch back.

RS485 Address

Read-only · 1 to 254 · default 1

The Modbus and RS485 slave address of the inverter. Read-only here, and the panel talks to the inverter at this ID.

USB tool access stops live data

Before it takes effect the panel warns that this releases the panel link to the inverter and that live data stops until you switch back, because only one connection can use the inverter at a time. The confirm button reads Release to USB. The switch is not saved, so a restart always returns the link to the panel.

Wi-Fi

The Wi-Fi page is a status and action screen rather than a settings list. It reports the connected network, IP address, signal strength and network time, and lists saved networks alongside the ones it can currently see. Scan for networks refreshes the list, and any saved network can be removed with Forget this network.

Restart the panel after saving a network

Saving a network does not finish the connection on its own. The panel offers a restart with a countdown, and connecting completes after that restart. If the saved network list is full, the panel says so and you will need to forget one before adding another.

Firmware Updates

The Firmware Update page, reached from System, has two independent sections. One updates the touchscreen panel. The other updates the inverter. They are separate processes with very different consequences, so check which section you are in before starting anything.

DANGER: Never interrupt an inverter firmware install

Before installing to the inverter the panel warns that the inverter will stop for about a minute and its output will be off. That warning also says, in capitals, not to remove power.

If power is lost part way through an inverter install, the inverter will not restart, and recovering it requires a qualified professional with bench equipment. Do not begin an inverter update during a storm, on an unstable supply, or when you cannot guarantee power for the duration.

Updating the Panel

The panel checks for updates over Wi-Fi, so connect it to a network first. The sequence runs from Check for updates through Download and install, and the status line reports each stage: checking, downloading, verifying, then installed and restarting. If a new version causes trouble, Revert to previous version goes back.

A dark screen during a panel update is normal

The panel warns before it starts: the screen turns off while the update downloads, and turns back on automatically when it is complete. This looks exactly like a failure and is not one. Leave it alone and let it finish.

Panel Update Messages

MessageWhat to do
Not connected to WiFiJoin a network in Settings, then check again.
Could not reach the update serverCheck the panel is on the right network and that the server is reachable.
The update server did not answer in timeThe network may be slow or the server busy. Try again.
The connection dropped part way throughMove closer to the access point, then try again.
The update server reported an errorNothing is wrong with the panel. Try again later.
The update server refused the requestThis panel may not be registered for updates. Contact your distributor.

Updating the Inverter

Inverter firmware is delivered by the panel across its link to the inverter, in three steps: Check inverter firmware, then Download to panel, then Install to inverter. Downloading to the panel is safe and can be done at any time. Only the final install step stops the inverter.

  1. Shut down or accept the loss of every load on the inverter output.
  2. Confirm the supply to the unit is stable and will not be interrupted.
  3. Download the new firmware to the panel first, and confirm it has arrived.
  4. Start the install and leave the unit completely alone until it reports completion.
  5. In a parallel system, update every unit so the versions match. Mismatched versions raise alarm code 42.

The update screen does not show release notes. To find out what changed in a version, check with your distributor rather than looking for notes on the panel.

Alarms & Fault Codes

The Alarms screen lists everything currently active, and reads No active alarms when the system is healthy. A new alarm interrupts with a popup that can be silenced or opened into the full list. Each alarm carries a code, a severity, a headline, and a description of what to do.

Severity Levels

Critical

Hard stop. The unit has shut down or is about to.

Fault

A real fault that affects operation and needs attention.

Warning

A heads-up. Often clears on its own, but worth understanding.

Information

Status reporting rather than a problem with the inverter.

Inverter Alarm Codes

CodeSeverityAlarm
1WarningBattery Voltage LowBattery voltage is below the warning threshold. Reduce load or recharge soon to avoid a shutdown.
2FaultBattery OvercurrentAverage battery current exceeded the safe limit. Reduce load; if it repeats, have the battery wiring checked.
3InfoBattery DisconnectedNo battery detected. Check the battery breaker, fuse, and cable connections.
4FaultBattery Empty (Cutoff)The battery reached the end-of-discharge cutoff and output was stopped. Recharge the battery.
5CriticalBattery Overcurrent (Hardware)Hardware detected excessive battery current and shut down to protect the unit. Disconnect the load and have the system inspected by a qualified professional.
6CriticalBattery OvervoltageBattery voltage is too high and can damage the inverter. Check charger settings and battery condition.
7CriticalDC Bus Overvoltage (Hardware)The internal DC bus voltage exceeded its hardware limit and the unit stopped to protect itself. Requires service by a qualified professional if it persists.
8CriticalDC Bus OvervoltageSoftware detected an over-voltage on the internal DC bus. This often follows a sudden load drop and should clear on restart.
9CriticalPV Voltage Too HighSolar input voltage exceeds the maximum. Reduce the number of panels in series or check the array wiring before reconnecting.
10CriticalPV OvercurrentSolar charge current exceeded the limit. Reduce PV input; if it repeats, have the array inspected.
11CriticalPV Overcurrent (Hardware)Hardware over-current on the solar charge stage. The unit stopped charging to protect itself.
12FaultInternal Comm Error (SPI)The internal processors lost SPI communication. Restart the unit; if it persists, service is required.
13FaultOverload on BypassThe load exceeds the bypass (utility) rating. Reduce the connected load.
14FaultInverter OverloadThe load exceeds the inverter rating. Reduce the connected load to avoid a shutdown.
15CriticalAC Overcurrent (Hardware)Hardware detected excessive AC output current, often from a short or inrush. Remove the load and restart.
16WarningProtection Stop RequestedThe auxiliary controller requested a PWM shutdown. This is usually momentary and should clear automatically.
17CriticalOutput Short CircuitA short circuit was detected on the AC output. Disconnect all loads and check the wiring before restarting.
18WarningDC Bus Soft-start FaultThe internal bus failed to pre-charge normally. Restart; if it repeats, service is required.
19FaultSolar Charger Over-temperatureThe solar (MPPT) stage is too hot and has reduced power. Improve ventilation and reduce load.
20FaultInverter Over-temperatureThe inverter heatsink is too hot. Improve ventilation; output resumes after it cools.
21CriticalCooling Fan FailureA cooling fan is not running. Clear any obstructions; a failed fan must be replaced by a qualified professional.
22CriticalMemory (EEPROM) ErrorStored settings could not be read or written. Re-check settings; if it persists, service is required.
23CriticalModel Configuration ErrorThe unit model configuration is invalid. Service by a qualified professional is required.
24FaultDC Bus ImbalanceThe positive and negative bus voltages differ too much. Restart; if it persists, service is required.
25CriticalDC Bus Short CircuitA short circuit was detected on the internal DC bus and the unit stopped. Service by a qualified professional is required.
26CriticalRelay FaultAn output relay is shorted or stuck. Service by a qualified professional is required.
27FaultCharger Over-temperatureThe line-charger stage is too hot and has reduced power. Improve ventilation and reduce charge current.
28WarningAC Input Phase ErrorThe utility input phase or wiring is incorrect. Check the line and neutral connections.
29FaultDC Bus UndervoltageThe internal DC bus voltage dropped too low, often under heavy load with a weak battery.
30WarningBattery Low (Warning)Battery state of charge is low. Recharge soon.
31WarningBattery Very LowBattery charge is very low. Output may stop soon; recharge now.
32FaultBattery Empty (Stopped)Output stopped because the battery charge is depleted. Recharge to resume.
33FaultControl CAN FaultThe internal control CAN bus lost communication. Restart; if it persists, service is required.
34WarningCommunication CAN FaultThe external communication CAN link was lost. Check the inter-unit or BMS CAN wiring.
35WarningParallel Address ErrorTwo units share the same parallel address, or an address is missing. Reassign unique addresses.
36WarningParallel Unit OffA unit in the parallel group is switched off or not responding. Check the other units.
37FaultParallel Current Sharing ErrorUnits in parallel are not sharing the load evenly. Check the parallel cables and settings.
38FaultParallel Battery MismatchBattery voltages differ between paralleled units. Verify all units share the same battery bank.
39WarningParallel AC Source MismatchParalleled units see different AC sources. Ensure all units share the same utility input.
40FaultParallel Sync ErrorUnits failed to synchronize in parallel. Check the sync and parallel cabling.
41FaultInverter DC Offset ErrorAbnormal DC voltage was detected on the inverter output. Restart; if it persists, service is required.
42FaultFirmware MismatchParalleled units are running different firmware versions. Update all units to the same version.
43FaultParallel Line Contactor ErrorThe parallel line contactor did not operate correctly. Service by a qualified professional is required.
44FaultSerial Number ErrorThe stored serial-number data is invalid. Service by a qualified professional is required.
45FaultParallel Mode FaultThe parallel operating mode is misconfigured. Review the parallel settings on all units.
46CriticalBMS Comms Lost, Shut DownThe BMS was in control and its communication link was lost, so the inverter shut down as configured. Check the BMS cable and protocol setting, then restart.
56FaultPV Isolation LowLow insulation resistance was detected on the solar array. Have the array and grounding checked by a qualified professional.
57CriticalGround Leakage CurrentExcessive ground leakage current was detected and output stopped for safety. Have the installation inspected by a qualified professional.
58InfoBMS Communication LostLost communication with the battery BMS. Check the BMS cable and the protocol setting.
59InfoBMS AlarmThe battery BMS reported an alarm. Check the battery and BMS for details.
60FaultBattery Under-temperature (BMS)The BMS reports the battery is too cold. Charging may be limited until it warms up.
61FaultBattery Over-temperature (BMS)The BMS reports the battery is too hot. Reduce charge and discharge, and improve ventilation.
62FaultBattery Overcurrent (BMS)The BMS reports excessive battery current. Reduce the load or charge current.
63FaultBattery Undervoltage (BMS)The BMS reports low battery voltage. Recharge the battery.
64InfoBattery Overvoltage (BMS)The BMS reports high battery voltage. Check charger settings.

Panel-Generated Alarms

These are raised by the touchscreen itself rather than by the inverter. The three shutdown warnings exist to give you a chance to act before the inverter trips.

CodeSeverityAlarm
200CriticalCommunication LostThe panel lost communication with the inverter. Check the RS485 and serial link, and that the inverter is powered on.
201CriticalShutdown Imminent: OverloadThe inverter is overloaded with no derating headroom left and is about to shut down. Reduce the load now.
202CriticalShutdown Imminent: Inverter HotThe inverter heatsink is within 5C of its trip point and is about to shut down. Reduce load and improve ventilation.
203CriticalShutdown Imminent: Transformer HotA transformer, buck, or battery sensor is within 5C of its trip point and the unit is about to shut down. Reduce load and improve ventilation.

Clearing alarms does not fix anything

The Clear Alarms button acknowledges what is on screen. If the underlying condition is still present the alarm returns immediately. Treat a repeating alarm as information rather than a nuisance, and work through the cause.

Protection Functions

These protections run automatically and are not user-configurable. Knowing they exist explains a lot of behavior that otherwise looks like a malfunction, particularly the ones that reduce power rather than stop.

ProtectionBehavior
PV current limitingWhen the array can produce more than the inverter is rated for, charging is held at the rated current and power rather than faulting.
PV overvoltageIf PV voltage exceeds the hardware maximum, the unit reports a fault and stops the solar stage.
Night reverse-chargeAfter dark, when battery voltage exceeds array voltage, the unit blocks the battery from discharging back into the panels.
AC input overvoltageIf the utility rises above the accepted window, charging from the grid stops and the unit transfers to inverter output.
AC input undervoltageIf the utility falls below the accepted window, charging from the grid stops and the unit transfers to inverter output.
Battery overvoltageAt the overvoltage disconnect threshold, both solar and grid charging stop to prevent overcharge damage.
Battery undervoltageAt the low-voltage disconnect threshold, discharge stops to protect the pack from deep discharge.
Battery overcurrentIf battery current exceeds the hardware limit, the output is turned off and discharge stops.
Output short circuitA short at the load terminals turns the AC output off immediately. Output is restored only after the fault is cleared and the unit is manually restarted.
Heatsink over-temperatureWhen internal temperature runs too high the unit stops charging and discharging, and resumes once it cools.
OverloadGraded by how far over the rating the load is. The output restores after about 3 minutes, and after five overload events it stays off until the unit is restarted.
AC backfeedPrevents inverter output feeding backward into the bypass AC input.
Bypass overcurrentThe built-in AC input circuit breaker protects the bypass path.
Bypass wiring errorIf the phase relationship on the AC input does not match the configured output, the unit refuses to connect to bypass, preventing a load outage or short at transfer.

How Overload Protection Is Graded

Load levelOutput turns off after
102% to 110% of rating5 minutes
110% to 125% of rating10 seconds
Above 125% of rating5 seconds

Two Output page settings change what happens next. Auto-restart on Overload and Auto-restart on Over-temp decide whether the unit attempts to come back by itself or latches off until someone restarts it. Bypass on Overload transfers the load to the utility instead of shutting down, whenever the grid is available.

Troubleshooting

SymptomLikely causeWhat to do
Screen is blankNo power reaching the unit, or the screen has timed outTouch the screen to wake it. If still blank, check the battery and PV disconnects are closed and the unit switch is on.
Settings tiles are grayed outUSB tool access has the inverter linkOpen Communication and switch USB tool access off. A restart also returns the link.
No response, check inverter linkThe panel cannot reach the inverterConfirm the inverter is powered, check the RS485 wiring, and confirm USB tool access is off.
A setting snaps back after changing itThe inverter refused the writePhase Configuration needs standby. Charge voltages can be refused while a BMS is in control. Check the row notes in this manual.
Standby will not clearA DC bus condition is still presentRead the standby reason on Live Data. If it says it will not clear on its own, the installation needs inspection.
Battery under-voltage alarmPack has fallen below the warning thresholdRecharge. Review Low DC Warning and Over-discharge Cutoff, and check whether the bank is sized for the load.
Battery shows as disconnectedBreaker open, loose cable, or the BMS is in protectionCheck the battery breaker and terminals, and confirm the BMS is communicating.
Inverter overloadConnected load exceeds the ratingReduce load and restart. Start large motor loads one at a time, smallest first.
Over-temperature on MPPT or inverterRestricted airflow, or high ambient temperatureClear the ventilation clearances, blow dust out of the unit with the power off, and reduce load until it cools.
Fan faultFan blocked or failedPower down and check for obstructions. A failed fan must be replaced by a qualified professional.
AC input phase errorInput phase does not match the output configurationMatch the input to the output. A split-phase output requires a split-phase input.
Relay fault after restartAn output relay is stuckPower down and restart once. If it returns, the unit needs service.
Generator keeps being rejectedInput window is too narrow for the sourceSet AC Input Range to Appliance (wide) and set Max AC Input Current to the generator rating.
BMS communication lostCable, protocol, or bus mismatchCheck the BMS cable, confirm the Battery Type selects the right bus, and confirm the BMS Protocol matches the battery documentation.
Panel will not find updatesNo Wi-Fi, or the server is unreachableJoin a network on the Wi-Fi page, restart the panel to finish connecting, then check again.
Parallel units disagreeAddress, firmware, wiring or configuration mismatchConfirm unique addresses, matching firmware on every unit, a shared battery bank and a single common AC source.

If a fault is not resolved by the steps above, contact support rather than opening the unit. Have the panel and inverter firmware versions from the About page, the alarm code, and a description of what the system was doing when the fault appeared.

Maintenance

Carry out the following checks twice a year, and more often in dusty, agricultural or coastal environments. Isolate every source before touching any wiring.

TaskInterval
Clear the airflow path around the unit and check the top vents are unobstructedTwice a year, more in dusty sites
Check wire insulation for sun damage, heat damage, cracking or rodent damageTwice a year
Inspect terminals for corrosion, discoloration or signs of overheating, and re-torque to specificationTwice a year
Confirm the readings on the panel match what the system is actually doingTwice a year
Check for insect nesting, dirt ingress and corrosion inside the terminal compartmentTwice a year
Blow dust out of the enclosure with canned air, with the unit fully powered downAnnually, more in dusty sites
Inspect any surge arrester and replace it if it has operatedTwice a year
Review the Alarms screen for anything recurringMonthly
Check for panel and inverter firmware updatesTwice a year

Clearing Dust from Inside the Enclosure

The top vents are unfiltered, so dust reaches the inside of the unit and settles on the heatsinks and the fans. A layer of dust acts as insulation, which raises operating temperatures and eventually causes the unit to derate or trip on over-temperature. Clearing it is straightforward, but it must be done with the unit completely dead.

DANGER: Fully power down before opening the enclosure

Isolate the battery, the PV array, and the AC input at their disconnects, and switch the unit off. Verify with a meter that the terminals are dead. Remember that a solar array is live in daylight and cannot be switched off at the panel.

The DC bus capacitors hold a charge after every source is isolated. Allow the unit to sit before opening it, and verify rather than assume. This is work for a qualified professional.

  1. Complete the full shutdown procedure, then isolate every source at its disconnect.
  2. Wait for the DC bus to discharge, and confirm with a meter before opening anything.
  3. Use dry canned air at low pressure, and keep the can upright so no liquid propellant is discharged into the unit.
  4. Blow from the inside outward where you can, so dust leaves through the vents rather than being driven deeper.
  5. Hold the fan blades still while blowing them. Spinning a fan with compressed air can overspeed and damage the bearing.
  6. Do not touch the board, the heatsinks, or any component with the nozzle, and never use a wet cloth or solvent inside the unit.
  7. Refit the terminal cover, then bring the system back up following the power-up procedure.

Repairable, but not while it is live

This unit is built to be repaired rather than discarded, and internal work including component-level repair is possible. What is not acceptable is opening it while any source is connected, or working inside it without the training to do so safely. Cleaning dust with the unit fully powered down is expected maintenance. Anything beyond that should go through your distributor so the work is recorded and the warranty position stays clear.

Commissioning Checklist

Work through this before handing the system over. The settings half matters as much as the wiring half, because a correctly wired system with the wrong battery profile will still damage a pack.

Mechanical and Electrical

  • Unit mounted level on solid structure, at a height where the screen is readable
  • Ventilation clearances satisfied on all sides, with nothing stacked against the unit
  • Chassis bonded to the grounding bus bar
  • Battery polarity verified with a meter before the disconnect was closed
  • PV string open circuit voltage measured and confirmed below the maximum at the coldest expected temperature
  • Each array landed on its own tracker, with no arrays paralleled across trackers or units
  • AC input phase relationship matches the configured output mode
  • All terminals torqued to specification with a calibrated tool
  • Terminal cover refitted and top vents clear
  • Disconnects and overcurrent protection installed and labeled

Panel Settings

  • Battery Type set to match the installed bank
  • For a smart battery: BMS Protocol set, and BMS Status reading Monitoring or In Control
  • For a BMS system: Fallback Settings reviewed and set, since they cannot be edited later while the BMS is talking
  • Capacity set to the actual bank size in amp-hours
  • Max Charge Current set at or below the battery vendor recommendation
  • Output Priority and Charger Source Priority chosen for the site
  • Output Voltage and Output Frequency confirmed against the loads
  • Max AC Input Current set to the breaker size, or the generator rating where applicable
  • Neutral bonding arrangement confirmed: bonded in the load panel, or input and output neutral on a common bus bar for an upstream bonded source. Exactly one bond in the system
  • Phase Configuration set on every unit, consistently across a parallel group
  • Wi-Fi joined and network time confirmed, if schedules will be used
  • Beeper set to something other than Silent where the unit is unattended
  • Panel and inverter firmware both up to date

Function Test

  • Power-up sequence completed in order, with no alarms raised
  • Live Data shows sensible values on every box: grid, load, battery, MPPT
  • Loads transfer to the inverter when the AC input is opened, and back when it is restored
  • Battery charges from the expected source for the chosen charge priority
  • Alarms screen reads No active alarms
  • Owner shown the Live Data screen, the Alarms screen, and how to shut the system down

Warranty

Before publishing: insert the warranty terms

Add the warranty period, what it covers, the claim procedure, and the registration requirement if there is one. The exclusions below are a starting point and need legal review.

What Is Not Covered

  • Damage caused by improper use, or by installation in an unsuitable location
  • Damage from a solar array whose open circuit voltage exceeds the maximum allowed
  • Operation outside the specified temperature range
  • Damage from reversed battery or PV polarity
  • Disassembly, modification or repair by anyone other than authorized service personnel
  • Damage occurring during transport or handling after delivery
  • Damage caused by failure to follow the installation and maintenance procedures in this manual

Before contacting support

Have the model and serial number, the panel and inverter firmware versions from the About page, the alarm code and severity, and a description of what the system was doing when the problem appeared. Photographs of the installation and the screen help considerably.